Free tool

Voltage drop calculator

Enter the supply, the load current and the cable. Get voltage drop in volts and percent, power lost as heat in the conductor, and the smallest standard cable size that meets your target.

Voltage drop calculator

1. Supply and load

V

Nepal and IEC single phase is 230 V. Use 400 V phase to phase for three phase, 120 V or 208 V for North America.

1.00 for a resistive load or an inverter at unity, 0.85 to 0.90 for a typical mixed load, 0.80 for motors.

Known quantity
A
W

2. Cable

Used only for the indicative current carrying capacity check below, not for the voltage drop maths.

mm²

Source to load distance, not the there and back loop. The calculator doubles it for you.

°C

20 °C for cold resistance, 70 °C for PVC cable at full load, 90 °C for XLPE, 100 °C for the conservative figure some codes use.

Advanced
Ω/m

0.00008 Ω/m is the standard default for multicore cable. Set to 0 to ignore reactance.

%

Results

Voltage drop
V
Voltage drop
%
Voltage at the load
V
Power loss in the cable
W
Power loss
%
Loop resistance
Ω
Resistivity used
Ω·mm²/m
Current / power

Voltage drop against cable size

Same current, length, material and temperature as above. The dashed line is your target of 3%.

1. Supply and load

V

For a PV string this is Vmp of one module times the number of modules in series. For a battery bank use 12, 24, 48 or the nominal DC bus voltage.

Known quantity
A

For a PV string use Imp of the module. For cable sizing many codes ask for 1.25 × Isc.

W

2. Cable

Used only for the indicative current carrying capacity check below, not for the voltage drop maths.

mm²

°C

Solar DC cable on a rooftop in Kathmandu regularly sits at 60 to 80 °C. Do not calculate a PV string at 20 °C.

Advanced
%

1% is normal practice for a PV string, 2% for the battery cable, 3% as an absolute maximum.

Results

Voltage drop
V
Voltage drop
%
Voltage at the load
V
Power loss in the cable
W
Power loss
%
Loop resistance
Ω
Resistivity used
Ω·mm²/m
Current / power

Voltage drop against cable size

Same current, length, material and temperature as above. The dashed line is your target of 1%.

Results are indicative and follow the IEC and NF C15-100 voltage drop method. The current carrying capacity note is a rough check against a simplified reference table of typical values, not a certified one, and neither replaces a short circuit withstand check or a protection coordination study. Always verify against the cable manufacturer's data and the wiring code that applies to your installation.

What voltage drop actually is

Every metre of cable has some resistance, so pushing current through it uses up a little of the supply voltage before that current ever reaches the load. The load ends up seeing less voltage than the source is putting out, and the difference is lost as heat in the cable itself rather than doing anything useful. That heat is also a real cost: it is electricity paid for and never received as light, torque or charge, for the whole life of the installation.

Left unchecked, an undersized cable shows up in different ways depending on what is at the end of it. A motor runs hotter and starts less reliably, since starting current is many times the running current and the drop is worst at exactly that moment. LED fittings dim or flicker once the supply to the driver falls outside its working range. A grid tied solar inverter can trip on overvoltage on a hot, high output afternoon, because it has to push its own terminal voltage even higher than the grid to export current through a cable that resists it. None of these show up as a fault on day one. They show up as a slow loss of performance and a shorter equipment life, which is why voltage drop is checked at design time rather than fixed after the fact.

The formula this calculator uses

This follows the standard IEC voltage drop method used across most of the world, and referenced directly by France's NF C15-100, in SI units:

ΔU = b × (ρ1 × L ÷ S × cosφ + λ × L × sinφ) × Ib

Where ΔU is the voltage drop in volts, b is 2 for single phase and DC circuits or 1 for three phase, ρ1 is the conductor resistivity at its actual operating temperature, L is the one way cable length in metres, S is the cross section in mm², λ is the reactance per metre, and Ibis the design current. Resistivity itself is temperature dependent: ρ1 equals ρ20times 1 plus α times the temperature rise above 20 °C, using the IEC 60228 constants for annealed copper and aluminium, the same constants that most national wiring codes point back to whether or not they publish their own local voltage drop formula.

How to use this calculator, step by step

Here is the whole process on one example: a single phase 230 V circuit carrying 16 A through 4 mm² copper cable, 40 metres one way, at 70 °C, power factor 0.90.

  1. Pick the AC circuit tab for mains wiring, or the DC tab for a battery or solar PV string.
  2. Enter the supply: system type, nominal voltage, and power factor for AC. Use 230 V single phase or 400 V three phase here.
  3. Enter the load as either a current or a power. 16 A is the design current in this example.
  4. Enter the cable: material, size, one way run length and conductor temperature. Here that is copper, 4 mm², 40 m, 70 °C.
  5. Read the results card: this example comes out at about 6.0 V dropped, 2.6 percent, and a Pass badge because it is inside the 3 percent target.
  6. Check the sizing note underneath. It tells you the smallest standard size that still meets your target, so you know if you have room to go smaller or need to go larger.
  7. Check the current carrying capacity note. It compares your design current against a typical reference rating for the size and installation method you picked, separate from the voltage drop result above it.
  8. If the result does not meet your target, either raise the target, choose a different size from the dropdown, or use the chart to see how drop falls as cross section increases.

Resistivity by material

Materialρ20 (Ω·mm²/m)α (per °C)ρ at 70 °C
Copper0.0172410.003930.02063
Aluminium0.0282640.004030.03396

Supply voltage by region

Enter whatever your own supply actually is. As a starting point, most of the world outside North America, including Nepal, India, the whole of Europe, the United Kingdom, Australia and most of Africa, standardised on 230 V single phase and 400 V three phase, phase to phase, under IEC 60038. North America runs 120 V single phase with a 240 V split phase supply to large appliances, and commercial buildings are commonly fed at 208 V three phase or 480 V three phase in industrial settings. Japan is the outlier, at 100 V single phase and 200 V three phase. None of this changes the formula, only the number in the voltage field.

How different wiring codes treat the same problem

Every major wiring code cares about voltage drop, though they differ in how strictly they enforce it. IEC 60364-5-52, used as the base standard across Europe, Nepal and most of Asia, gives 3 percent for a final circuit and 5 percent overall as recommended limits. The UK's BS 7671 adopts the same IEC figures directly. The US National Electrical Code gives 3 and 5 percent as an informational note rather than a hard requirement, so it is treated as best practice rather than something an inspector fails a job over. Canada's CSA C22.1 and Australia's AS/NZS 3000 both reference broadly similar figures. Whichever code applies to a given job, a cable that clears roughly 3 percent on a final circuit and 5 percent overall will satisfy essentially all of them.

Current carrying capacity: the check most drop calculators skip

A cable can pass every voltage drop target and still be dangerous, because voltage drop and current carrying capacity are two separate limits. Drop is about the length of the run and how much of the supply you can afford to lose along it. Capacity is about how much current the conductor and its insulation can carry continuously before the cable itself overheats, and it barely cares about length at all. Most free voltage drop tools, including the one that inspired parts of this page, stop at the drop calculation and leave the capacity check as a separate step you have to do yourself, usually in a different tool entirely. This calculator folds a first pass at that second check into the same result, using the installation method you select next to the cable material.

The table below gives typical current ratings for PVC insulated copper cable at 70 °C, in the same format used across most IEC based wiring codes: reference method A1, enclosed in conduit or trunking in an insulated wall, and reference method C, clipped direct or run in free air. For aluminium, this calculator applies a commonly used approximation of 0.78 times the copper rating for the same size and method, since aluminium's higher resistance sheds less heat for the same cross section.

Size (mm²)Method A1, enclosedMethod C, free air
1.514.5 A19.5 A
2.519.5 A27 A
426 A36 A
634 A46 A
1046 A63 A
1661 A85 A
2580 A112 A
3599 A138 A
50119 A168 A
70151 A213 A
95182 A258 A
120210 A299 A
150240 A344 A
185273 A392 A
240321 A461 A

Treat these as typical, indicative figures rather than a rating you can build to. Real current carrying capacity depends on the specific cable construction, ambient temperature, how many other loaded cables it runs alongside, and whether it touches thermal insulation, and manufacturers publish correction factors for all four. Use this table to catch an obviously undersized cable early, then confirm the final size against the manufacturer's datasheet, such as a cable maker's own catalogue, and the wiring code that applies to your installation.

Two worked examples

A single phase 230 V circuit carrying 16 A through 4 mm² copper cable, 40 metres one way, at 70 °C, power factor 0.90. Resistivity at that temperature works out to about 0.0206 Ω·mm²/m, and the voltage drop comes to roughly 6.0 V, about 2.6 percent, comfortably inside the usual 3 percent target for a final circuit.

A common North American case tells a different story. A 120 V, 20 A circuit run 30 metres, about 100 feet, one way, is often wired in 10 AWG copper on the assumption that the size is already generous for the current. At 60 °C that cable actually comes out to about 3.8 percent drop, past the usual 3 percent target, and the next size up, 8 AWG, brings it back to about 2.4 percent. The lesson holds everywhere: a cable sized only for current rating, with no separate check on length, quietly fails on longer runs. Run the same current through a solar water pump instead and the story changes again: an undersized DC string cable can lose several percent of the array's output before it ever reaches the inverter, which is exactly why the solar pump sizing guide treats cable sizing as a real design step, not an afterthought.

Frequently asked questions

What is an acceptable voltage drop?

Aim for 3 percent or less on a final circuit and 5 percent or less from the origin of the installation to the load, which is what IEC 60364-5-52 recommends. On solar DC strings the working target is tighter: 1 percent is normal practice and 3 percent should be treated as an absolute ceiling, because every volt lost in the string cable is energy the array never delivers.

Should I enter the one way length or the total loop length?

Enter the one way length, meaning the distance from the source to the load along the cable route. The calculator applies the length factor itself: it doubles the run for single phase and DC circuits because current flows out and back, and uses the single run for three phase circuits.

Why does the calculator ask for conductor temperature?

Copper and aluminium both become more resistive as they heat up, by roughly 0.4 percent per degree Celsius. A cable carrying its full rated current sits far above ambient, so a calculation done at 20 degrees understates the real drop by around a fifth. Use 70 degrees for PVC cable at full load, 90 degrees for XLPE, and 100 degrees for the conservative figure some codes use.

What resistivity values does this calculator use?

It starts from the IEC 60228 values for annealed conductors at 20 degrees Celsius: 0.017241 ohm mm2 per m for copper and 0.028264 for aluminium. It then corrects for temperature using rho1 equals rho20 times 1 plus alpha times T minus 20, with alpha at 0.00393 per degree for copper and 0.00403 for aluminium. At 70 degrees that works out to about 0.02063 for copper and 0.03396 for aluminium.

Why is the power loss percentage different from the voltage drop percentage on AC?

On a DC circuit the two are identical, since loss divided by input power reduces to the same expression as drop divided by voltage. On AC they separate for two reasons: reactance adds to the voltage drop without dissipating any power, and power factor means the current producing the I squared R heating is larger than the current the load actually converts to useful work. At a power factor of 0.9 the loss percentage runs roughly a tenth higher than the drop percentage.

Can I use this calculator for AWG wire sizes?

Yes. Switch the size field from mm2 to AWG and pick a gauge from 20 AWG up to 500 kcmil. The tool converts to the equivalent metric cross section internally and shows the mm2 figure it used, so you can check it against a cable datasheet in either system.

Does a low voltage drop mean the cable is correctly sized?

No. Voltage drop is only one of four checks. The cable must also carry the design current continuously without exceeding its insulation temperature, withstand the prospective short circuit current for the time the protective device takes to operate, and let that device trip within the required disconnection time. A cable can pass on voltage drop and still be dangerously undersized on the other three.

How do I calculate voltage drop for a solar PV string?

Use the DC tab. Set the voltage to Vmp of one module multiplied by the number of modules in series, and the current to Imp of the module, since a series string carries the module current regardless of how many modules it has. Set the temperature to 70 degrees or higher for cable clipped to a rooftop rail, and enter the run from the far end of the string to the inverter or combiner box.

What about voltage drop on the AC side of an inverter?

Use the AC tab with the inverter's rated output current and a power factor of 1.0, unless the inverter is set to supply reactive power, in which case use its actual displacement factor. Grid tied inverters raise their terminal voltage to push current out, so an oversized drop on the AC cable shows up as nuisance overvoltage tripping on hot sunny afternoons rather than as a dim light.

Is aluminium cable a reasonable substitute for copper?

Electrically, aluminium needs roughly 1.6 times the cross section of copper for the same resistance, so a 25 mm2 copper conductor is replaced by 35 or 50 mm2 aluminium. It is markedly cheaper per amp carried and is standard for larger feeders and service cables. The trade offs are physical rather than electrical: aluminium creeps under a terminal screw, so it needs correctly rated bimetallic lugs and torque checks, and it takes more room in a conduit.

What voltage should I enter for a Nepali installation?

Nepal Electricity Authority supplies 230 V single phase and 400 V three phase at 50 Hz, matching the IEC standard, so enter 230 for a domestic circuit and 400 for a three phase supply. Bear in mind that supply voltage in parts of the distribution network already sits low, which leaves less headroom for drop in your own wiring than the nominal figure suggests.

How much money does voltage drop actually cost?

Take the loss in watts from the results, multiply by the number of hours the circuit runs each year, and divide by 1000 to get kilowatt hours. A 15 kW pump losing 668 W in an undersized cable and running 2000 hours a year burns about 1336 kWh, which is real money at any tariff, and it continues for the whole life of the installation. That comparison is usually what justifies the larger cable.

Does this calculator check whether my cable can safely carry the current?

It gives you an indicative check, not a certified one. Pick an installation method and the result panel compares your design current against typical reference current ratings for that conductor size and material. Treat it as a first pass: it does not correct for ambient temperature, grouping with other loaded cables, or thermal insulation, so the manufacturer's rated current table and your local wiring code remain the final word.